3500/42 Operation and Maintenance
Configuration Information
41
CP Mod
Selecting the CP Mod button in the Channel Options Dialog Box, allows a
Custom channel configuration to be downloaded to the monitor. Custom
configuration data is stored in a Custom Products Modification File. Custom
Products Modification files follow the naming convention <modification #.mod>.
These files must be located in the \3500\Rackcfg\Mods\ directory. When a CP
Mod file is selected, a window is displayed which describes the function of the
modification. CP Mod files are available through Bently Nevada's Custom
Products Division. Contact your local Bently Nevada Sales Representative for
details.
Reference Information
These fields contain information that indicates which module you are configuring.
Channel
The number of the channel being configured (1 through 4).
Slot
The location of the monitor in the 3500 rack (2 through 15).
Rack Type
Identifies the type of Rack Interface Module installed (Std or TMR).
Enable
Peak to Peak
The difference between the positive and the negative extremes of the rotor
bow. The proportional value is only available when a Keyphasor channel has
been selected. This value may be displayed in mils or
µ
m.
Direct
The instantaneous eccentricity value. The direct value can be displayed
three ways:
- At shaft rotative speeds greater than 600 rpm, the direct value is the
average distance between the probe tip and the shaft and is displayed
in a way similar to a thrust measurement. This direct measurement is
displayed only when Direct Channel Above 600 rpm is enabled.
- At shaft rotative speeds between 600 rpm and the rpm setting for
Instantaneous Crossover, the direct measurement consists of two
values: a maximum and minimum value relative to a zero reference.
These two direct values are called Direct Max and Direct Min.
- At shaft rotative speeds less than the rpm setting for Instantaneous
Crossover, Direct Max and Direct Min are equal and the direct
measurement consists of an instantaneous measurement relative to a
zero reference. This type of direct measurement is called
instantaneous gap.