Configuration Information
3500/42 Operation and Maintenance
24
Transducer Orientation
Degrees
The location of the transducer on the machine. The range for orientation
angle is 0 to 180 degrees left or right as observed from the driver to the
driven end of the machine train. Refer to the following figure:
This drawing is for horizontal shafts.
Barriers
Select the MTL 796(-) Zener External option, or Galvanic Isolators if external
safety barriers are connected between the monitor and the transducer. If using
an Internal Barrier I/O Module, select the internal option. These devices are
used to restrict the amount of energy that can flow into a hazardous area.
3.1.3
Thrust Position Channel Options
This section discusses the Configuration Considerations and the Rack
Configuration Software screens associated with the Thrust Position Channel.
3.1.3.1
Thrust Position Channel Configuration Considerations
Consider the following items before configuring a Thrust Position Channel:
- Internal Barrier I/O Modules are not currently supported with 7200 11 mm or
14 mm, or 3000 Proximitors, or the 3300 16 mm HTPS.
- The "No Keyphasor" option is automatically selected for this channel type.
No Keyphasors are required.
- The Thrust Direct full-scale range is dependent upon the transducer type.
- The Zero Position voltage range is dependent upon the direct full-scale
driver end
180
°
90
°
right
90
°
left
driven end
shaft
0
°
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com