3500/42 Operation and Maintenance
I/O Module Descriptions
77
4.2
Proximitor/Seismic I/O Module (Internal
Termination)
Internal Termination I/O modules require you to wire each transducer and
recorder directly to the I/O module. This section shows what this Internal
Termination I/O module looks like and how to connect the wires to the Euro Style
connector.
Connect the wire from the
transducers associated with
Channel 1 and 2 to the I/O
module.
INHB/RET: Connect to an
external switch. Used to
inhibit all non-primary
Alert/Alarm 1 functions for all
four channels.
COM/REC: Connect each
channel of the I/O module to
a recorder.
Connect the wire from the
transducers associated with
Channel 3 and 4 to the I/O
module.
Use the jumper to
select the type of
transducer connected
to Channel 3 and 4 of
the I/O module.
Use the jumper to
select the type of
transducer connected
to Channel 1 and 2 of
the I/O module.