Configuration Information
3500/42 Operation and Maintenance
46
Scale Factor
Transducer
Without
Barriers
With Bently
Nevada Internal
Barriers
Standard I/O
With
Barriers
Discrete TMR
I/O With
Barriers
Bussed TMR
I/O With
Barriers
3300 5 and 8 mm
7200 5 and 8 mm
200 mV/mil
200 mV/mil
192 mV/mil
200 mV/mil
199 mV/mil
7200 11 mm
100 mV/mil
*
*
*
*
7200 14 mm
100 mV/mil
*
*
*
*
3300 16 mm HTPS
100 mV/mil
*
*
*
*
Note: ±15 % scale factor adjustment allowed.
* Barriers are not supported with this transducer option.
OK Limits
Transducer
Upper
Lower
Center Gap Voltage
Without
Barriers
(V)
With
Barriers
(V)
Without
Barriers
(V)
With
Barriers
(V)
Without
Barriers
(V)
With
Barriers
(V)
3300 8 mm
3300 5 mm
7200 5 mm
7200 8 mm
-16.75
-16.75
-2.75
-2.75
-9.75
-9.75
7200 11 mm
-19.65
*
-3.55
*
-11.60
*
7200 14 mm
-16.75
*
-2.75
*
-9.75
*
3300 16 mm
HTPS
-16.75
*
-2.75
*
-9.75
*
* Barriers are not supported with this transducer option.
Note: With Barriers includes BNC Internal Barrier I/O Modules.
Transducer Jumper Status (on I/O Module)
Returns the position of the Transducer Jumper on the Proximitor/Seismic I/O
Module. Refer to Section 4.1 (Setting the I/O Jumper) for the function of this
jumper.
Alarm Mode
Latching
Once an alarm is active, it will remain active even after the proportional value
drops below the configured setpoint level. The channel will remain in alarm
until it is reset using one of the following methods:
- the reset switch on the front of the Rack Interface Module
- the contact on the Rack Interface I/O Module
- the Reset button in the Operator Display Software
- the reset command through the Communication Gateway Module
- the reset command through the Display Interface Module
- the reset command in the Rack Configuration Software