3500/42 Operation and Maintenance
Configuration Information
27
Reference Information
These fields contain information that indicates which module you are configuring.
Channel
The number of the channel being configured (1 through 4).
Slot
The location of the monitor in the 3500 rack (2 through 15).
Rack Type
Identifies the type of Rack Interface Module installed in the rack (Standard or
TMR).
Enable
Direct
Average position, or change in position, of a rotor in the axial direction with
respect to some fixed reference. This value may be displayed in mils or
µ
m.
This proportional value supports both center zero and noncenter zero Full
Scale Ranges.
Gap
The physical distance between the face of a proximity probe tip and the
observed surface. The distance is expressed in terms of voltage. Standard
polarity convention dictates that a decreasing gap results in an increasing
(less negative) output signal.
Direct Full Scale Ranges by transducer type
3300 - 5 and 8 mm Proximitor
7200 - 5 and 8 mm Proximitor
7200 - 11 and 14 mm Proximitor
3300 - 16 mm HTPS
Nonstandard
3000 (-18V) Proximitor
3000 (-24V) Proximitor
3300 RAM Proximitor
25-0-25 mil
30-0-30 mil
40-0-40 mil
0.5 - 0 - 0.5 mm
1.0 - 0 - 1.0 mm
Custom
25-0-25 mil
30-0-30 mil
40-0-40 mil
50-0-50 mil
75-0-75 mil
0.5 - 0 - 0.5 mm
1.0 - 0 - 1.0 mm
2.0 - 0 - 2.0 mm
Custom
25-0-25 mil
0.5 - 0 - 0.5 mm
Custom
The Gap Full Scale Ranges are the same for all transducer types.
Gap
-24 Vdc
Custom