3500/42 Operation and Maintenance
Configuration Information
21
Trip Multiply
The value selected to temporarily increase the alarm (Alert and Danger) setpoint
values. This value is normally applied by manual (operator) action during startup
to allow a machine to pass through high vibration speed ranges without monitor
alarm indications. Such high vibration speed ranges may include system
resonances and other normal transient vibrations.
Direct Frequency Response
The upper and lower corners for the band-pass filter used with direct vibration
measurements. The available ranges are 240 to 240,000 cpm and 60 to 36,000
cpm.
Transducer Selection
The following transducer types are available for the Radial Vibration Channel
(non-barrier I/O module):
3300 – 5 mm Proximitor
3300 – 8 mm Proximitor
7200 – 5 mm Proximitor
7200 – 8 mm Proximitor
7200 – 11 mm Proximitor
7200 – 14 mm Proximitor
3000 (-18 V) Proximitor
3000 (-24 V) Proximitor
3300 RAM Proximitor
3300 – 16 mm HTPS
Nonstandard
The following transducer types are available for the Radial Vibration Channel
(barrier I/O module):
3300 – 5 mm Proximitor
3300 – 8 mm Proximitor
7200 – 5 mm Proximitor
7200 – 8 mm Proximitor
3300 RAM Proximitor
Nonstandard
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com