3500/42 Operation and Maintenance
Maintenance
101
still indicates an Alarm.
9. Adjust the function generator amplitude such that the signal reads below the
Over Alarm setpoint levels. If the nonlatching option is configured, observe
that the bar graph indicator for Direct changes color to green and that the
Current Value Box contains no indication of alarms. Press the RESET switch
on the Rack Interface Module (RIM) to reset latching alarms.
10. If you can’t verify any configured alarm, recheck the configured setpoints. If
the monitor still does not alarm properly or fails any other part of this test, go
to Section 5.1.11 (If a Channel Fails a Verification Test).
11. Disconnect the test equipment and reconnect the PWR, COM, and SIG field
wiring to the channel terminals on the I/O module. Verify that the OK LED
comes on and the OK relay energizes. Press the RESET switch on the Rack
Interface Module (RIM) to reset the OK LED.
12. Repeat steps 1 through 11 for all configured channels.
Gap
1. Disconnect PWR, COM, and SIG field wiring from the channel terminals on
the I/O module.
2. Connect test equipment and run software as described in Section 5.1.5.1
(Test Equipment and Software Setup - Radial Vibration).
3. Adjust the power supply to produce a voltage that is within the Gap setpoint
levels on the Gap bar graph display of the Verification screen.
4. Press the RESET switch on the Rack Interface Module (RIM). Verify that the
OK LED is on, the bar graph indicator for Gap is green and that the Current
Value field has no alarm indication.
5. Adjust the power supply voltage such that the signal just exceeds the Gap
Over Alert/Alarm 1 setpoint level. Wait for 2 or 3 seconds after the alarm
time delay expires and verify that the bar graph indicator for Gap changes
color from green to yellow and that the Current Value Field indicates an
Alarm.
6. Press the RESET switch on the Rack Interface Module (RIM). Verify that the
bar graph indicator for Gap remains yellow and that the Current Value Field
still indicates an Alarm.
7. Adjust the power supply such that the signal just exceeds the Gap Over
Danger/Alarm 2 setpoint level. Wait for 2 or 3 seconds after the alarm time
delay expires and verify that the bar graph indicator for Gap changes color
from yellow to red and that the Current Value Field indicates an Alarm.
8. Press the RESET switch on the Rack Interface Module (RIM). Verify that the
bar graph indicator for Gap remains red and that the Current Value Field still
indicates an Alarm.