3500/42 Operation and Maintenance
Troubleshooting
193
6.2
LED Fault Conditions
The following table shows how to use the LED’s to diagnose and correct
problems.
OK Led
TX/RX
BYPASS
Condition
Solution
1 Hz
1 Hz
Monitor is not
configured, is in
Configuration Mode, or
in Calibration Mode.
Reconfigure the
Monitor, or exit
Configuration, or
Calibration Mode.
5 Hz
Monitor error
Check the System
Event List for severity.
ON
Flashing
Module is operating
correctly
No action required.
OFF
Monitor is not operating
correctly or the
transducer has faulted
and has stopped
providing a valid signal.
Check the System
Event List and the
Alarm Event List.
2 Hz
Monitor is configured for
Timed OK Channel
Defeat and has been not
OK since the last time
the RESET button was
pressed.
Press the Reset
button on the Rack
Interface Module.
Check the System
Event List.
Not
flashing
Monitor is not operating
correctly.
Monitor is not
executing alarming
functions. Replace
immediately.
OFF
Alarm Enabled
No action required.
ON
Some or all Alarming
Disabled
No action required.
= Behavior of the LED is not related to the condition.