Configuration Information
3500/42 Operation and Maintenance
44
If the 100 ms option is on (
):
- The Danger time delay is set to 100 ms.
- The Danger time delay can only be set for the primary proportional
value.
Direct Channel Above 600 RPM
Disabled
Display and alarming of the Direct proportional value will be disabled when
the shaft rotative speed exceeds 600 rpm.
Enabled
Display and alarming of the Direct proportional value will remain active when
shaft rotative speed exceeds 600 rpm.
Zero Position (Direct)
Represents the transducer DC voltage corresponding to the zero indication on
the channel's meter scale for the direct proportional value. The amount of
adjustment allowed is dependent upon the Direct Full Scale Range and the
transducer OK limits. To ensure maximum amount of zero adjustment, gap the
probe as close as possible to the center gap voltage specified in the OK Limit
table.
Adjust Button
Adjust the Zero Position voltage. When this button is clicked a utility starts that
helps you set the direct zero position voltage. Since this utility provides active
feedback from the 3500 rack, a connection with the rack is required. Refer to
Section 5.2 (Adjusting the Scale Factor and the Zero Position).
Transducer
The following transducer types are available for the Eccentricity Channel (non-
barrier I/O module):
3300 – 5 mm Proximitor
3300 – 8 mm Proximitor
3300 – 16 mm HTPS
7200 – 5 mm Proximitor
7200 – 8 mm Proximitor
7200 – 11 mm Proximitor
7200 – 14 mm Proximitor
Nonstandard
The following transducer types are available for the Eccentricity Channel (barrier
I/O module):
3300 – 5 mm Proximitor
3300 – 8 mm Proximitor
7200 – 5 mm Proximitor
7200 – 8 mm Proximitor
Nonstandard