Configuration Information
3500/42 Operation and Maintenance
64
Scale Factor
Transducer
Without Barriers
With BNC Internal
Barriers
With Barriers
9200
500 mV/(in/s)
*
500 mV/(in/s)
47633
490 mV/(in/s)
*
490 mV/(in/s)
86205
477 mV/(in/s)
*
477 mV/(in/s)
Nonstandard 2 wire
145 mV/(in/s)
*
145 mV/(in/s)
Velomitor
100 mV/(in/s)
100 mV/(in/s)
100 mV/(in/s)
High Temperature
Velomitor
145 mV/(in/s)
145 mV/(in/s)
145 mV/(in/s)
Note: ±15 % scale factor adjustment allowed.
* Barriers are not supported with this transducer option.
OK Limits
Transducer
Upper
Lower
Center Gap Voltage
Without
Barriers
(V)
With
Barriers
(V)
Without
Barriers
(V)
With
Barriers
(V)
Without
Barriers
(V)
With
Barriers
(V)
9200
-17.95
-17.95
-2.05
-2.05
-10.00
-10.00
47633
-17.95
-17.95
-2.05
-2.05
-10.00
-10.00
86205
-17.95
-17.95
-2.05
-2.05
-10.00
-10.00
NonStandard
-17.95
-17.95
-2.05
-2.05
-10.00
-10.00
Velomitor
-19.85
-17.95
-19.85
†
-4.15
-2.05
-4.15
†
-12.00
-10.00
-12.00
†
High
Temperature
Velomitor
-21.26
-21.26
-2.74
-2.74
-12.00
-12.00
* Barriers are not supported with this transducer option.
†
BNC Internal Barrier I/O Modules.
Transducer Jumper Status (on I/O Module)
Returns the position of the Transducer Jumper on the Proximitor/Seismic I/O
Module. Refer to Section 4.1 (Setting the I/O Jumper) for the function of this
jumper.
Take Input From Channel A (1 or 3) Transducer
The Channel B (2 or 4) Velocity channel options screen has an extra control that appears
just above the transducer type list box (see figure below). It is the Take Input from Channel
A Transducer checkbox. When checked (
), the channel pair uses Dual Path Input. That
is, input from the first channel (1 or 3) is used for both channels in the pair. The transducer
input, barrier, OK Mode, and Timed OK Channel Defeat input from channel A will be copied
to the second channel (2 or 4) in the channel pair.