3500/42 Operation and Maintenance
Configuration Information
15
- There are two selections for 3000 Series transducers:
3000(-24V) Proximitor
Select this option when connecting a 3000 Series proximitor directly to a
3500 monitor. A default scale factor of 285 mV/mil will be selected. This
may be adjusted ±15 %. Note that the buffered transducers on the front
of the monitors and to the Data Manager are not compensated and
should be interpreted at 285 mV/mil.
3000(-18V) Proximitor
Select this option when connecting a 3000 Series proximitor directly to a
3500 monitor, but supplying proximitor power from an external 18 volt
source. A default scale factor of 200 mV/mil will be selected. This may
be adjusted ±15 %. Note that the buffered transducers on the front of the
monitors and to the Data Manager are not compensated and should be
interpreted at 200 mV/mil.
- Setpoints may only be set on proportional values which are enabled.
Monitors must be configured in channel pairs (for example, Channels 1 and 2
may be configured as Radial Vibration and Channels 3 and 4 may be
configured as Thrust Position).
- When a full-scale range is modified, the setpoints associated with this
proportional value should be readjusted.
- It is best to set the Scale Factor value and the Trip Multiply value before the
Zero Position value.
- 3000 (-18V), 3000 (-24V), and 3300 RAM Proximitors have limited linear
ranges. Therefore, you should use caution when selecting the Full-scale
range of the Direct, 1X Amplitude (Ampl), 2X Amplitude (Ampl), Not 1X
Amplitude (Ampl) and S
max
Amplitude (Ampl) PPLs. Full-scale value x Trip
Multiply should not exceed the linear range of the transducer.