Configuration Information
3500/42 Operation and Maintenance
42
Instantaneous Crossover
The value for shaft rotative speed where the direct eccentricity measurement
changes from Direct Max/ Direct Min to instantaneous gap. The value for
Instantaneous Crossover must be between 1 and 10 rpm.
Gap
The physical distance between the face of a proximity probe tip and the
observed surface. The distance is expressed in terms of voltage. Standard
polarity convention dictates that a decreasing gap results in an increasing
(less negative) output signal.
Peak to Peak Full Scale Ranges by transducer type
3300 - 5 and 8 mm Proximitor
7200 - 5 and 8 mm Proximitor
7200 - 11 and 14 mm Proximitor
3300 – 16 mm HTPS
Nonstandard
0-5 mil pp
0-10 mil pp
0-20 mil pp
0-30 mil pp
0-100
µ
m pp
0-200
µ
m pp
0-500
µ
m pp
Custom
0-5 mil pp
0-10 mil pp
0-20 mil pp
0-30 mil pp
0-50 mil pp
0-100
µ
m pp
0-200
µ
m pp
0-500
µ
m pp
0-1000
µ
m pp
Custom
Direct Full Scale Ranges by transducer type
3300 - 5 and 8 mm Proximitor
7200 - 5 and 8 mm Proximitor
7200 - 11 and 14 mm Proximitor
3300 – 16 mm HTPS
Nonstandard
5-0-5 mil
10-0-10 mil
20-0-20 mil
30-0-30 mil
100-0-100
µ
m
200-0-200
µ
m
500-0-500
µ
m
Custom
5-0-5 mil
10-0-10 mil
20-0-20 mil
30-0-30 mil
50-0-50 mil
100-0-100
µ
m
200-0-200
µ
m
500-0-500
µ
m
1000-0-1000
µ
m
Custom
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com