![background image](http://html1.mh-extra.com/html/bently-nevada/proximitor-3500-42/proximitor-3500-42_operation-and-maintenance-manual_2735487076.webp)
3500/42 Operation and Maintenance
Configuration Information
69
Setpoint
Number
Eccentricity
Acceleration
Velocity
1
Over Peak to Peak
Over Direct
Over Direct
2
Over Gap
Danger (Over Direct)
Danger (Over Direct)
3
Under Gap
4
Over Direct Max
5
Under Direct Max
6
Over Direct Min
7
Under Direct Min
8
Danger (configurable)
9
Danger (configurable)
10
Danger (configurable)
11
Danger (configurable)
All the Alert/Alarm 1 setpoints are provided first, followed by the configured
danger setpoints.
Example 1:
Radial Vibration with the Danger/Alarm 2 Over 2X Ampl setpoint and the
Danger/Alarm 2 Under 2X Ampl setpoint selected.
Alert/Alarm 1 setpoints:
setpoints 1 through 13
Danger/Alarm 2 setpoints:
setpoint 14 is Over 2X Ampl (Danger)
setpoint 15 is Under 2X Ampl (Danger)
Example 2:
Thrust Position with the Danger/Alarm 2 Over Gap setpoint and the
Danger/Alarm 2 Under Gap setpoint selected.
Alert/Alarm 1 setpoints:
setpoints 1 through 4
Danger/Alarm 2 setpoints:
setpoint 5 is Over Gap (Danger)
setpoint 6 is Under Gap (Danger)