3500/42 Operation and Maintenance
Maintenance
181
Acceleration Default OK Limits Table
Transducer
Lower Ok Limit
(Volts)
Upper Ok Limit
(Volts)
23733-03 w/o barriers
-2.7 to -2.8
-15.0 to -15.1
23733-03 w/ barriers
-3.05 to -3.15
-2.7 to -2.8 *
-13.8 to -13.9
-15.0 to -15.1 *
49578-01 w/o barriers
-5.58 to -5.68
-11.32 to -11.42
49578-01 w/ barriers
-5.29 to -5.39
-5.58 to -5.68 *
-10.81 to -10.91
-11.32 to -11.42 *
24145-02 w/o barriers
-2.7 to -2.8
-15.0 to -15.1
155023-01 w/o barriers
-5.58 to -5.68
-11.32 to -11.42
330400 w/ barriers
-3.05 to -3.15
-2.7 to -2.8 *
-13.8 to -13.9
-15.0 to -15.10 *
330400 w/o barriers
-2.7 to -2.8
-15.0 to -15.10
330425 w/ barriers
-5.29 to -5.39
-5.58 to -5.68 *
-10.81 to -10.91
-11.32 to -11.42 *
330425 w/o barriers
-5.58 to -5.68
-11.32 to -11.42
Note: Assume ±50 mV accuracy for check tolerance.
* = BNC Internal Barrier I/O Modules.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com