Configuration Information
3500/42 Operation and Maintenance
40
- External barriers are not currently supported with 7200 11 mm, 14 mm, or
3300 16 mm HTPS.
- Monitors must be configured in channel pairs (for example Channels 1 and
2 may be configured as Eccentricity and Channels 3 and 4 may be
configured as Thrust Position).
- When a full-scale range is modified, the setpoints associated with this
proportional value should be readjusted.
- The Peak to Peak proportional value is disabled when "No Keyphasor" is
selected on the Four Channel Proximitor/Seismic Monitor screen.
- The Latching OK Mode and the Timed OK Channel Defeat options are not
compatible.
- If a Non-Standard transducer is selected, the setpoint OK limits are set to
±1 volt from the Upper and Lower OK limits that are selected.
3.1.5.2
Eccentricity Channel Configuration Options
This section describes the options available on the Eccentricity Channel
configuration screen.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com