3500/42 Operation and Maintenance
Configuration Information
39
Transducer Jumper Status (on I/O Module)
Returns the position of the Transducer Jumper on the Proximitor/Seismic I/O
Module. Refer to Section 4.1(Setting the I/O Jumper)for the function of this
jumper.
Alarm Mode
Latching
Once an alarm is active, it will remain active even after the proportional value
drops below the configured setpoint level. The channel will remain in alarm until
it is reset using one of the following methods:
- the reset switch on the front of the Rack Interface Module
- the contact on the Rack Interface I/O Module
- the Reset button in the Operator Display Software
- the reset command through the Communication Gateway Module
- the reset command through the Display Interface Module
- the reset command in the Rack Configuration Software
Nonlatching
When an alarm is active, it will go inactive as soon as the proportional value
drops below the configured setpoint level. Alert should be the first level alarm
that occurs when the transducer signal level exceeds the selected value.
Danger should be the second level alarm that occurs when the transducer
signal level exceeds the selected value. The Alert and Danger values are set
on the Setpoint screen.
Upscale Direction
Towards or away from the probe mounting. This field defines whether rotor
movement toward or away from the differential expansion corresponds to a more
positive differential expansion (for example upscale on a bar graph). If this field
is set to "Toward Probe", then as the rotor moves toward the differential
expansion probe the differential expansion direct proportional value will increase
and go upscale on a bar graph.
3.1.5
Eccentricity Channel Options
This section discusses the Configuration Considerations and the Rack
Configuration Software screens associated with the Eccentricity Channel.
3.1.5.1
Eccentricity Channel Configuration Considerations
Consider the following items before configuring an Eccentricity Channel:
- Internal Barrier I/O Modules are not currently supported with 7200 11 mm or
14 mm, 3000 Proximitors, 3300 16 mm HTPS, or 3300 RAM.
- If a Keyphasor channel is selected, a Keyphasor Module must be installed
in the rack.
- The full-scale options allowed for each proportional value is dependent
upon the transducer type.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com