Maintenance
3500/42 Operation and Maintenance
136
WARNING
Application Alert
High voltage present.
Contact could cause
shock, burns, or death.
Do not touch exposed
wires or terminals.
Tests will exceed alarm
setpoint levels causing
alarms to activate. This
could result in a relay
contact state change.
Application Alert
Disconnecting field
wiring will cause a not
OK condition.
Test Equipment Setup - Eccentricity
Simulate the transducer signal by connecting the power supply, function
generator and multimeter to COM and SIG of channel 1 with polarity as shown in
the figure on page 137 Eccentricity Test Setup). Set the test equipment as
specified below:
Power Supply
Function Generator
-7.00 Vdc
Waveform: sinewave
DC Volts: 0 Vdc
Frequency: 5 Hz
Amplitude level: Minimum (Above
Zero)