3500/42 Operation and Maintenance
Maintenance
107
8. Press the RESET switch on the Rack Interface Module (RIM). Verify that the
bar graph indicator for 2X Phase remains red and that the Current Value
Field still indicates an Alarm.
9. Adjust the phase such that the reading is below the Over Alarm setpoint
levels. If the nonlatching option is configured, observe that the bar graph
indicator for 2X Phase changes color to green and that the Current Value Box
contains no indication of alarms. Press the RESET switch on the Rack
Interface Module (RIM) to reset latching alarms.
10. Repeat steps 3 through 9 to test the Under Alert/Alarm 1 and Under
Danger/Alarm 2 setpoints by adjusting the phase to exceed the Under Alarm
setpoint levels.
11. If you can not verify any configured alarm, recheck the configured setpoints.
If the monitor still does not alarm properly or fails any other part of this test,
go to Section 5.1.11 (If a Channel Fails a Verification Test).
12. Disconnect the test equipment and reconnect the PWR, COM, and SIG field
wiring to the channel terminals on the I/O module. Verify that the OK LED
comes on and the OK relay energizes. Press the RESET switch on the Rack
Interface Module (RIM) to reset the OK LED.
13. Repeat steps 1 through 12 for all configured channels.
Not 1X Amplitude (Not 1X)
Note
The Keyphasor must be triggering and have a valid rpm value to check this
parameter.
1. Disconnect PWR, COM, and SIG field wiring from the channel terminals on
the I/O module.
2. Connect test equipment and run software as described in Section 5.1.5.1
(Test Equipment and Software Setup - Radial Vibration).
3. Set the Keyphasor multiplier/divider so that the multiply setting is one and the
divide setting is two. Adjust the function generator amplitude to produce a
reading that is below the Not 1X setpoint levels on the Not 1X bar graph
display of the Verification screen.
4. Press the RESET switch on the Rack Interface Module (RIM). Verify that the
OK LED is on, the bar graph indicator for Not 1X is green, and the Current
Value field has no alarm indication.
5. Adjust the function generator amplitude such that the signal just exceeds the
Not 1X Over Alert/Alarm 1 setpoint level. Wait for 2 or 3 seconds after the
alarm time delay expires and verify that the bar graph indicator for Not 1X
changes color from green to yellow and that the Current Value Field indicates
an Alarm.