3500/42 Operation and Maintenance
I/O Module Descriptions
81
4.5.2
Proximitor/Seismic TMR I/O Module (External Termination)
The Proximitor/Seismic TMR I/O Module is used in a TMR rack and can be
configured as TMR I/O Discrete or TMR I/O Bussed.
When configured as TMR I/O Discrete, twelve transducers send input signals to
three monitors so that each transducer signal of each channel is not shared by
other channels. Six External Termination Blocks are required: three are
Proximitor/Seismic External Termination Blocks used to wire the transducers; the
other three are Recorder External Termination Blocks used to wire the recorders.
When configured as TMR I/O Bussed, four transducers are bussed to three
monitors so that each transducer is shared by three channels, one channel from
each monitor. Four External Termination Blocks are required: one is a Bussed
Proximitor/Seismic External Termination Block used to wire the transducers; the
other three are Recorder External Termination Blocks used to wire the recorders.
Connect the I/O module to the External Termination
Block using cable 129525-XXXX-XX
Connect the I/O module to the Recorder External
Termination Blocks using cable 129529-XXXX-XX
Use the jumper to select the type of transducer
connected to Channel 1 and 2 of the I/O module.
Use the jumper to select the type of transducer
connected to Channel 3 and 4 of the I/O module.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com