3500/42 Operation and Maintenance
Configuration Information
35
Rack Type
Identifies the type of Rack Interface Module installed in the rack (Standard or
TMR).
Enable
Direct
Change in position of the shaft due to the thermal growth relative to the
machine casing. This value may be displayed in inches or mm. This
proportional value supports both center zero and noncenter zero Full Scale
Ranges.
Gap
The physical distance between the face of a proximity probe tip and the
observed surface. The distance is expressed in terms of voltage. Standard
polarity convention dictates that a decreasing gap results in an increasing
(less negative) output signal.
Direct Full Scale Ranges by transducer type
25 mm Extended Range Proximitor
35 mm Extended Range Proximitor
50 mm Extended Range Proximitor
Nonstandard
5-0-5 mm
0-10 mm
0.25 - 0 - 0.25 in
0.0 - 0.5 in
Custom
5-0-5 mm
0-10 mm
10-0-10 mm
0-20 mm
0-25 mm
0.25 - 0 - 0.25 in
0.0 - 0.5 in
0.5 - 0 - 0.5 in
0.0 - 1.0 in
Custom
The Gap Full Scale Ranges are the same for all transducer types.
Gap
-24 Vdc
Custom
Clamp Value
The value that a proportional value goes to when that channel or proportional
value is Bypassed or defeated (For example when a problem occurs with the
transducer). The selected value can be between the minimum and maximum
full-scale range values. Only the values available from the Recorder Outputs,
Communication Gateway and Display Interface Module are clamped to the
specified value when the proportional value is invalid.