3500/42 Operation and Maintenance
Configuration Information
31
Transducer
Scale Factor
Without
Barriers
With Bently
Nevada Internal
Barriers
Standard I/O
With
Barriers
Discrete TMR
I/O With
Barriers
Bussed TMR
I/O With
Barriers
3300 5 and 8 mm
7200 5 and 8 mm
200 mV/mil
200 mV/mil
192 mV/mil
200 mV/mil
199 mV/mil
7200 11 mm
100 mV/mil
*
*
*
*
7200 14 mm
100 mV/mil
*
*
*
*
3000 (-18V)
200 mV/mil
*
*
*
*
3000 (-24V)
285 mV/mil
*
*
*
*
3300 RAM
200 mV/mil
200 mV/mil
192 mV/mil
200 mV/mil
199 mV/mil
3300 16 mm HTPS
100 mV/mil
*
*
*
*
Note: ±15 % scale factor adjustment allowed.
* Barriers are not supported with this transducer option.
OK Limits
Transducer
Upper
Lower
Center Gap Voltage
Without
Barriers
(V)
With
Barriers
(V)
Without
Barriers
(V)
With
Barriers
(V)
Without
Barriers
(V)
With
Barriers
(V)
3300 8 mm
3300 5 mm
7200 5 mm
7200 8 mm
-19.04
-18.20
-1.28
-1.10
-1.28
†
-10.16
-9.65
-9.74
†
7200 11 mm
-20.39
*
-3.55
*
-11.97
*
7200 14 mm
-18.05
*
-1.65
*
-9.85
*
3000 (-18V)
-13.14
*
-1.16
*
-7.15
*
3000 (-24V)
-16.85
*
-2.25
*
-9.55
*
3300 RAM
-13.14
-12.35
-1.16
-1.05
-1.16
†
-7.15
-6.7
-6.76
†
3300 16 mm
HTPS
-18.05
*
-1.65
*
-9.85
*
* Barriers are not supported with this transducer option.
†
BNC Internal Barrier I/O Modules.