Maintenance
3500/42 Operation and Maintenance
138
Verification Screen Setup - Eccentricity
Run the Rack Configuration Software on the test computer. Choose Verification
from the Utilities menu and choose the proper Slot number and Channel number
then click on the Verify button.
Note
If the Timed OK Channel Defeat is enabled, the OK LED will not come on
immediately after you connect the test equipment. It will take 60 seconds for a
channel to return to the OK status from not OK. If OK mode is configured for
latching, press the RESET button on the Rack Interface Module (RIM) to return
to the OK status.
The following table directs you to the starting page of each maintenance section
associated with the Eccentricity Channels.
Section
Number
Topic
Page
Number
5.1.7.2
Test Alarms - Peak to Peak
139
5.1.7.2
Test Alarms - Gap
140
5.1.7.2
Test Alarms - Direct
141
5.1.7.3
Verify Channel Values - Peak to Peak
142
5.1.7.3
Verify Channel Values - Gap
143
5.1.7.3
Verify Channel Values - Direct
144
5.1.7.4
Test OK Limits
146
5.1.7.2
Test Alarms - Eccentricity
The general approach for testing alarm setpoints is to simulate the eccentricity
signal with a function generator and power supply. The alarm levels are tested
by varying the output from the test equipment and observing that the correct
results are reported in the Verification screen on the test computer. It is only
necessary to test those alarm parameters that are configured and being used.
The general test procedure to verify current alarm operation will include
simulating a transducer input signal and varying this signal:
1.
to exceed over Alert/Alarm 1 and Danger/Alarm 2 Setpoints.
2.
to drop below any under Alert/Alarm 1 and Danger/Alarm 2 Setpoints.
3.
to produce a nonalarm condition.