Maintenance
3500/42 Operation and Maintenance
104
Note
The 1X Amplitude needs to be a minimum of 100 mV to get a valid 1X Phase
reading.
4. Press the RESET switch on the Rack Interface Module (RIM). Verify that the
OK LED is on, the bar graph indicator for 1X Phase is green, and the Current
Value field contains no alarm indication.
5. Adjust the phase such that the reading just exceeds the 1X Phase Over
Alert/Alarm 1 setpoint level. Wait for 2 or 3 seconds after the alarm time
delay expires and verify that the bar graph indicator for 1X Phase changes
color from green to yellow and the Current Value Field indicates an Alarm.
6. Press the RESET switch on the Rack Interface Module (RIM). Verify that the
bar graph indicator for 1X Phase remains yellow and that the Current Value
Field still indicates an Alarm.
7. Adjust the phase such that the reading just exceeds the 1X Phase Over
Danger/Alarm 2 setpoint level. Wait for 2 or 3 seconds after the alarm time
delay expires and verify that the bar graph indicator for 1X Phase changes
color from yellow to red and that the Current Value Field indicates an Alarm.
8. Press the RESET switch on the Rack Interface Module (RIM). Verify that the
bar graph indicator for 1X Phase remains red and that the Current Value
Field still indicates an Alarm.
9. Adjust the phase such that the reading is below the Over Alarm setpoint
levels. If the nonlatching option is configured, observe that the bar graph
indicator for 1X Phase changes color to green and that the Current Value Box
contains no indication of alarms. Press the RESET switch on the Rack
Interface Module (RIM) to reset latching alarms.
10. Repeat steps 3 through 9 to test the Under Alert/Alarm 1 and Under
Danger/Alarm 2 setpoints by adjusting the phase to exceed the Under Alarm
setpoint levels.
11. If you can not verify any configured alarm, recheck the configured setpoints.
If the monitor still does not alarm properly or fails any other part of this test,
go to Section 5.1.11 (If a Channel Fails a Verification Test).
12. Disconnect the test equipment and reconnect the PWR, COM, and SIG field
wiring to the channel terminals on the I/O module. Verify that the OK LED
comes on and the OK relay energizes. Press the RESET switch on the Rack
Interface Module (RIM) to reset the OK LED.
13. Repeat steps 1 through 12 for all configured channels.