Description of the Software Modules and Parameters
Parameter manual
b maXX
BM5800
Document No.: 5.16029.03
635
3
166.18
State frequency reduction
166.19
Frequency reduction
Decrease of the frequency in Hz without reduction of the voltage.
166.20
Additional voltage
Additional voltage due to the current control at low frequencies
166.21
Frequency f0
Threshold frequency from which the slope of the voltage is linear. The threshold frequen-
cy is calculated from the Zero voltage (
) and the slope of the U-f characteristic.
166.22
Reference frequency
Reference frequency [Hz] = Additional frequency (
+ Frequency of ramp generator (
)
- Frequency reduction (
)
166.23
Additional frequency
Additional frequency [Hz] from the compensating controller
Value
Meaning
0
Inactive
1
Counter
2
Frequency reduction
3
Increase of frequency with compensating controller for acceleration
4
Voltage reduction
5
Increase of frequency with simple overcurrent protection
Содержание b maXX BM5800
Страница 10: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 10 of 814 Contents ...
Страница 724: ...Monitoring Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 724 of 814 3 11 ...
Страница 756: ...Error descriptions Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 756 of 814 4 5 ...
Страница 800: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 800 of 814 ...
Страница 808: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 808 of 814 ...
Страница 814: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 814 of 814 Notes ...
Страница 815: ......