Configuration
Parameter manual
b maXX
BM5800
Document No.: 5.16029.03
Baumüller Nürnberg GmbH
118
3.4
138.32
Peak current derating
Derating of the peak current of the drive is required for special devices (see
from page 61 and parameter
bit 6).
138.34
Torque base value
(from FW version 1.14)
Reference value of the standardized torque parameters.
The torque reference value M
base
was specified the maximum, internal motor torque that
would be available due to a torque current of the same amount as the maximum total cur-
rent
.
with:
I
s max
"Max. drive current"
Flux
nom
Nominal magnetic flux, 100%
Kt
, in Nm/A
Asynchronous motors or synchronous motors in the field weakening range cannot reach
this torque because of the field current which is required.
The parameter is the reference value of the standardized set value
146.1
Asynchronous motor mode
Bit string to select the control mode of an asynchronous motor
M
base
I
s max
Kt
Flux
nom
100
--------------------
I
s max
Kt
=
=
Bit no.
Meaning
7 ... 0
Reserved
8
Build-up of the flux before the transition in drive manager state 4
(
):
1: on
0: off
9
Reserved
10
Command start of the Lh-identification
15 ... 11
Reserved
Содержание b maXX BM5800
Страница 10: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 10 of 814 Contents ...
Страница 724: ...Monitoring Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 724 of 814 3 11 ...
Страница 756: ...Error descriptions Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 756 of 814 4 5 ...
Страница 800: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 800 of 814 ...
Страница 808: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 808 of 814 ...
Страница 814: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 814 of 814 Notes ...
Страница 815: ......