3.4
150.22
Target number output PID controller 2
Selection of the target of the PID controller output.
All cyclic writable parameters are permitted.
150.23
Kp PID controller 2
Proportional gain of the PID controller 2.
150.24
Tn PID controller 2
Integral action time of the PID controller 2.
150.25
Td PID controller 2
Derivative time of the PID controller 2.
150.26
Pt1 time constant PID controller 2
Time constant of the PT1 filter in the D leg of the PID controller. If the value „0“ is speci-
fied, the signal will be transmitted unfiltrated.
150.27
Output upper limit PID controller 2
Upper limit of the PID controller output.
If the output is limited with this limit, it will be signalized in
bit 4.
NOTE!
If the upper limit is greater than the maximum value of the linked target parameter,
then the output is limited at writing on the target parameter to the maximum value of
the linked target parameter if necessary. This will be signalized in
bit 8.
Содержание b maXX BM5800
Страница 10: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 10 of 814 Contents ...
Страница 724: ...Monitoring Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 724 of 814 3 11 ...
Страница 756: ...Error descriptions Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 756 of 814 4 5 ...
Страница 800: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 800 of 814 ...
Страница 808: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 808 of 814 ...
Страница 814: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 814 of 814 Notes ...
Страница 815: ......