Description of the Software Modules and Parameters
Parameter manual
b maXX
BM5800
Document No.: 5.16029.03
149
3
In addition, an automatic identification of the correction values is possible in ProDrive.
The current and the speed must be entered during the identification (
) for this
purpose. The evaluation is determined by a constant current input. The present status is
displayed in
3.4.6.7 SSI digital configuration
The complete transmission cycle must be processed within 61.5 µs. For this, the trans-
mission speed
bits 10 to 13, the number of the bits to be transmitted
(
), the parity bit (
bit 16) as well
as the monoflop time t
m
of the encoder are relevant (refer to the according encoder data
sheet).
Parity bit
Up to a maximum of 48 bit data + optional parity bit can be transmitted. In case the parity
bit shall be evaluated, it must be transmitted as the last bit (least-significant bit / LSB). If
the encoder transmits the parity bit at another position then it must be considered as a
data bit and goes into the 48-bit limitation. Then the parity bit is not be checked.
Additional data
If the encoder transmits additional data before and/or after the encoder position, these
can be filed in any scalar and cyclically writable parameters.
If the additional data is not relevant for the application, then the bit number (
) is specified, only - the target parameter however is left empty.
Additional data can be transmitted before the position (MSB) or after the position (LSB).
Sample configuration
= 6
6 bit data before the position
= 8
8 bit revolutions
16 bit angle
18 bit data after the position
Z
126.21
–
Application parameter Uint16_1
Z
126.61
–
Application parameter Uint32_1
T
P106.62
P106.63
P106.98
P106.99
P106.60 bit 16
+
+
+
+
P106.60 bit 10...13 in Hz
--------------------------------------------------------------------------------------------------------------------------------------------
t
m
61.5
s
+
=
NOTE!
When transmitting in the gray code format the additional data is decoded, as well!
Содержание b maXX BM5800
Страница 10: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 10 of 814 Contents ...
Страница 724: ...Monitoring Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 724 of 814 3 11 ...
Страница 756: ...Error descriptions Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 756 of 814 4 5 ...
Страница 800: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 800 of 814 ...
Страница 808: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 808 of 814 ...
Страница 814: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 814 of 814 Notes ...
Страница 815: ......