Controllers
Parameter manual
b maXX
BM5800
Document No.: 5.16029.03
Baumüller Nürnberg GmbH
470
3.7
47.8
Tn q-current controller
Integral action time of the q-current controller,
Units: ms
For description, see
.
47.9
Kp d-current controller 4kHz
Proportional gain of the d-current controller at 4 kHz PWM frequency,
Units: V/A
According to the optimum magnitude and taking account of the internal standardizations,
Kp and Tn for the Id current controller at 4 kHz PWM frequency can be set as follows:
T
n
= L
sd
/ r
s
(ms)
where r
s
= Stator resistance in ohms, cold
k
p
= L
sd
/(3*Tab) = L
sd
/(3*0.125) = 2.667* L
sd
(L
sd
in mH)
For asynchronous motors, the total leakage inductance L
sigma
must be used instead of
L
sd
.
47.10
Tn d-current controller
Integral action time of the d-current controller,
Units: ms
For description, see
.
47.20
Usq set value
Displays the control variable for the iq controller, taking account of the feedforward.
47.21
Usd set value
Displays the control variable for the id controller, taking account of the feedforward.
47.22
Integral term Usq
Displays the integration terms of the control variable for the iq controller.
Содержание b maXX BM5800
Страница 10: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 10 of 814 Contents ...
Страница 724: ...Monitoring Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 724 of 814 3 11 ...
Страница 756: ...Error descriptions Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 756 of 814 4 5 ...
Страница 800: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 800 of 814 ...
Страница 808: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 808 of 814 ...
Страница 814: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 814 of 814 Notes ...
Страница 815: ......