3.7
Dead time voltages
Dead time voltages are non-linear occurrences in the output voltage of the converter. This
can have several causes such as the locking time when switching the IGBTs, differences
of on and off times of the IGBTs and diodes and the threshold voltages of the IGBTs and
diodes. These non-linear voltages distort the voltage output of the PWM modulator. They
are considerably low compared to the nominal motor voltage. However, the encoderless
procedures and the accuracy of power displays that are based on the motor voltage - in
particular at lower speeds - can be affected.
Friction effects
Friction is a contrary-focused force which is non-linear to the motor movement (torque).
It is dependent of the moving direction as well as the condition (motor moves or stops). It
is compensated by the integral component of the speed controller. The friction can be pre-
controlled by an additive additional torque set value by the controller so that it does not
have to be compensated by the integral component, especially if the direction is changed.
This results in a lower tracking error.
The stick-slip phenomenon is a jerking motion due to alternation between sticking and
sliding. The phenomenon can be compensated by an adaption of the P and I components
of the speed controller.
This is described in detail in
Torque ripples
Synchronous motors provide torque ripples; these are the forces between the magnet
and the teeth that cause an irregular running. If the torque ripples are dependent of an
electrical angle they can be compensated by an additional torque current in the controller.
This is described in detail in
3.7.7.1 Parameter Overview of the Controller Adaptations
Functional blocks:
FbStromBegr [138]
Functional blocks:
FbReglerAdaption [155]
Number
Name
Type
Min
Max
Default Value
Unit
Factor
Read
only
St
o
ra
g
e
DS Sup
port
Cyclic W
rite
Axis-
inde
pend
ent
138.23
Kt correction factor
FLOAT
0
100
1
1:1
X
155.1
Mode
UINT
0
0xFFFF
0
1:1
X
155.2
State
UINT
0
0xFFFF
0
1:1
X
155.10
Ks actual value
FLOAT
0.01
1e9
1e4
Grad/
s
2
/A
1:1
X
155.14
Ks adaption cyclic
UDINT
UDINT
0xFFFFFFFF 65536
%
655.36:
1
X
X
155.24
Kt actual value
FLOAT
0.0
1000.00
0.00
Nm/A
1:1
X
Содержание b maXX BM5800
Страница 10: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 10 of 814 Contents ...
Страница 724: ...Monitoring Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 724 of 814 3 11 ...
Страница 756: ...Error descriptions Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 756 of 814 4 5 ...
Страница 800: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 800 of 814 ...
Страница 808: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 808 of 814 ...
Страница 814: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 814 of 814 Notes ...
Страница 815: ......