Motor Operating Mode
Parameter manual
b maXX
BM5800
Document No.: 5.16029.03
Baumüller Nürnberg GmbH
670
3.9
3.9.2
Sensorless control for asynchronous motors (open loop)
3.9.2.1 Sensorless control, at stator flux oriented
The drive controller b maXX
5800 permits an operation of an asynchronous motor in
speed control without a rotary encoder (open loop control). However, a position controlled
operation (operating modes position control, synchronous operation, positioning, etc.) or
a pure torque control is not possible.
The open loop control operation is based upon calculating the speed of an asynchronous
motor from its model. For this purpose, the motor data (as e. g. inductance and resis-
tance) must be exactly known. The motor commutation operates stator-field oriented here
in contrast to the operation of an asynchronous motor with an encoder whereby the elec-
trical variables of the motor is oriented towards the rotor field.
The motor voltages are not measured, but the voltage set values, which were calculated
from the motor control, are used instead. The dead time compensation must also be ac-
tivated, so that the nonlinearity of the power unit can be compensated.
The reliability of open loop operation at low frequencies below 2 Hz is compromised by
the accuracy of motor model parameters and compensation of power unit nonlinearity.
Therefore, for applications requiring persistent operation in this region, it is recommended
to use the closed loop control with an encoder.
m
Motoring operation at very low speeds (output frequency below 2 Hz) should be avoid-
ed.
m
Generating operation at very low speeds (output frequency below motor rated slip)
should be avoided.
m
Change of speed direction without load is possible.
m
Generating operation until standstill is possible.
m
A longer lasting generator-based operation (1-2 s) at very low speeds is not possible.
m
The persistent operation at zero frequency is not possible.
m
Operation with motors connected parallel is not possible.
Performance specifications
Frequency operation limits:
m
Minimum output operation frequency motoring mode f
min_m
= 2.0 Hz
m
Minimum output operation frequency regenerating mode f
min_r
= motor rated slip
m
Maximum output operation frequency f
max
= 150 Hz
Performance of closed-loop speed control:
m
Control range = 1:100
m
Static accuracy =
30% of motor rated slip
m
Maximum speed regulation bandwidth = 15 Hz
Содержание b maXX BM5800
Страница 10: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 10 of 814 Contents ...
Страница 724: ...Monitoring Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 724 of 814 3 11 ...
Страница 756: ...Error descriptions Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 756 of 814 4 5 ...
Страница 800: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 800 of 814 ...
Страница 808: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 808 of 814 ...
Страница 814: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 814 of 814 Notes ...
Страница 815: ......