Description of the Software Modules and Parameters
Parameter manual
b maXX
BM5800
Document No.: 5.16029.03
255
3
Torque init stress on master and slave-side as torque additional set value
The torque init stress is parameterized and calculated on the master axis and is connect-
ed to the output of the speed controller. In addition it will be sent via cross communication
to the slave on which it is connected to the output of the speed controller also.
The torque init stress acts symmetrically on the master and the slave axis.
Figure 72:
Structure of the control of the torque coupling at connecting the torque coupling as torque addi-
tional set value
x
x
-
0
P147.4 Bit 0
0
1
P147.13
P147.9
P147.10
P147.7
P147.8
P147.6
P147.5
P147.18
-
-
-
0,5
0,5
Compensating controller
Coupling
factor
slave
Coupling
factor
master
Slave
Master
Cross communication
Stress
ns
et
m
set,slave
n
act
m
P147.19
set,master
Coupling
command
P147.4
T
orque
init
stress
actual
value
P147.20
Torque init
stress Mv
n
act
m
set,master
Содержание b maXX BM5800
Страница 10: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 10 of 814 Contents ...
Страница 724: ...Monitoring Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 724 of 814 3 11 ...
Страница 756: ...Error descriptions Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 756 of 814 4 5 ...
Страница 800: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 800 of 814 ...
Страница 808: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 808 of 814 ...
Страница 814: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 814 of 814 Notes ...
Страница 815: ......