Error descriptions
Parameter manual
b maXX
BM5800
Document No.: 5.16029.03
Baumüller Nürnberg GmbH
744
4.5
1000
Power unit has canceled the controller
activation
Error is triggered in the module Operating Type Manager when a
power unit error has occurred.
m
Cause / Remedy:
- Check motor cable
- Check motor connection
- Replace power unit
n
Effect:
The error is fatal and leads to the immediate deactivation of the
drive controller. The drive will fizzle out, if applicable. Controller
activation for the drive again will be prevented until the error
cause has been eliminated and the error has been reset.
Pulse block
1001
Bridge short circuit
The error is triggered when the IGBT switch sequence monitoring of
the pulse width modulation does not detect a permitted status.
Faulty and critical statuses may be bridge short circuit or inactive
periods that were not complied with.
Pulse block
1002
Power unit maximum DC link voltage
exceeded
The actual value of the DC link voltage is displayed through Parame-
ter 130.03.
When a limit that is defined by the power unit is exceeded (see
Parameter
), the power unit will switch off with error.
m
Cause / Remedy:
- Continuous braking operation of the axes
- Error on chopper connection / chopper resistor
n
Effect:
The error is fatal and leads to the immediate deactivation of the
drive controller. The drive will fizzle out, if applicable.
Controller activation for the drive again will be prevented until the
error cause has been eliminated and the error has been reset.
Pulse block
1003
Overcurrent error in the power unit
The limit of the maximum current of the power unit is exceeded in
one of the three phases.
In the additional information 1 of the error message is shown in
which channel the overcurrent was recognized:
0: Overcurrent (from mono device power unit)
1: Channel A, positive
2: Channel A, negative
3: Channel B, positive
4: Channel B, negative
5: Channel C, positive
6: Channel C, negative
m
Cause/ Remedy:
Check motor leads
Check motor connection
Pulse block
Error
num-
ber
Brief error text
Error description
Default set-
ting for
Error
Response
Содержание b maXX BM5800
Страница 10: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 10 of 814 Contents ...
Страница 724: ...Monitoring Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 724 of 814 3 11 ...
Страница 756: ...Error descriptions Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 756 of 814 4 5 ...
Страница 800: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 800 of 814 ...
Страница 808: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 808 of 814 ...
Страница 814: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 814 of 814 Notes ...
Страница 815: ......