GUID-540639DC-734D-45B7-ACAC-9B00C7A1A9D5 V1 EN
Figure 468:
IEC 61850 Configuration Editor Reporting Status Dataset Dialog Screen
Reporting Trigger Options – (for both Unbuffered and Buffered report
control blocks)
Schema 1.4 does not support General Interrogation. Schema 3.0 does
support General Interrogation.
GUID-4D93A983-857E-4D9C-99AA-FA0DBB94B2BF V1 EN
Figure 469:
Report Trigger Options Dialog Screen
•
Data Change/Data Update – For measurements, if the value of the data attribute
exceeds (either lower or higher) the deadband value the report is generated. For
status, if the value of the data attributes changes, the report is generated.
•
Data Update – is treated the same as Data Change.
•
Quality Change – For any measurement or status, the source is a PROCESS. The
settings are SUBSTITUTED values.
If system error or checksum error is detected, the validity are questionable and inaccurate.
If self test fails, then validity is Invalid. Good means there is no abnormal condition of the
1VAC388793-MB A
Section 13
Appendix D IEC 61850 Configuration Editor
TCC300
683
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......