Setting Programmable Alarm relay mode from the HMI
The "Auto/Man Switch Type Selection" in configuration must be set to
"SCAMP" to access this setting.
1.
Press the Down Arrow (CNFG Hot Button) pushbutton to wake the unit. The menu
will advance to "CONFIGURATION".
2.
Press the Down Arrow pushbutton once. The unit will display the following:
Tapchanger Type
3.
Press the Right or Left arrow pushbutton, as necessary, to navigate to the
"Programmable Alarm" menu.
4.
Press the Down arrow pushbutton, as necessary, until the "Programmable Alarm
Function" screen is displayed.
5.
Press the ENT pushbutton. If prompted, enter a valid Level 2 Access Code. The
following will be displayed:
Prog Alarm Function
NORMAL C
6.
Utilizing the arrow pushbuttons, select the desired Programmable Alarm Function
Mode (NORMAL or AS DEADMAN OUT), then press the ENT pushbutton.
Setting Programmable Alarm relay mode from TCC600
The "Auto/Man Switch Type Selection" in configuration must be set to
"SCAMP" to access this setting.
1.
Select
Setup/Configuration
from the TCC600 toolbar. TCC600 will display the
Configuration dialog screen.
1VAC388793-MB A
Section 6
Configuration
TCC300
331
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......