6.4.1.10
Initializing Tap Position When Motor Direct Drive KeepTrack
TM
"INTERNAL KEEPTRACK" is Active from TCC600
When the Motor Direct Drive Internal KeepTrack tap position method is
used, it must be calibrated for proper voltage control with Reverse Power
Operation.
1.
Select
Setup/Tap Settings
from the TCC600 toolbar. TCC600 will display the Tap
Settings dialog screen.
GUID-2EDBFD25-222B-4846-9AA2-CDFA5AE21B47 V1 EN
Figure 365:
Tap Settings Dialog Screen
2.
Verify that "INTERNAL KEEPTRACK" is selected in the "General" section of the
dialog screen.
In order to verify Neutral Tap Position, when the tap position is "0",
but no neutral input is detected, the Tap Position screen of the
TCC300 will display "- - -" instead of "0". When reading the tap
position via comms (Modbus and DNP) a value of 32767 will be
returned when the tap position is "0", but no neutral input is detected,
otherwise a "0" will be returned.
3.
Determine and note the actual tap position from the external tap position indicator on
the regulator or transformer.
Section 6
1VAC388793-MB A
Configuration
464
TCC300
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......