10.1. Adjust the Master tap position by initiating a tapchange as necessary to bring
the Master Band Status "In-Band" from the Master, Remote Control dialog
screen "Tap Control" section.
10.2. Drive each Follower tap position in the Master/Follower scheme to match the
Master tap position.
10.3. Select "Master" from the Master, "Master/Follower Configuration" section of
the "Configuration" dialog screen.
After placing the Master control in "Master" the Master will
not respond to any tapchange requests for 32 seconds.
10.4. When at least 32 seconds have elapsed, initiate a Raise or Lower tapchange
from the Master, Remote Control dialog screen "Tap Control" section.
10.5. Verify that all Followers initiate tapchanges to match the Master tap position.
10.6. If necessary, return the Master to an "In-Band" tap position.
10.7. Select "Unblock" from the Master, Remote Control dialog screen "Remote
Operation/Block Auto Control via Communication (Comm Block)" section.
11. The Master/Follower Paralleling scheme is now in effect.
6.3.2.6
Setting of masters and followers from the HMI
A minimum of 2 controls are required for the paralleling scheme to work. The Master unit
will be configured first and then the Follower(s).
Setting up Master Control from the HMI
This procedure requires Level 2 Access.
1.
Verify that the appropriate Setup Settings have been entered for the control
application.
2.
Place the Master Control to be setup in Manual.
3.
Press the Down Arrow (CNFG Hot Button) pushbutton to wake the unit. The menu
will advance to "CONFIGURATION".
4.
Press the Down Arrow pushbutton once. The unit will display the following:
Tapchanger Type
5.
Press the Right or Left arrow pushbutton, as necessary, to navigate to the
"Paralleling" menu.
6.
Press the Down arrow pushbutton, as necessary, until the "Paralleling Type" screen
is displayed.
Section 6
1VAC388793-MB A
Configuration
422
TCC300
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......