4.
Press the Down arrow as necessary until the "Highest (Lowest) Tap" screen is
displayed.
5.
Press the ENT pushbutton. If prompted, enter a valid Level 2 Access Code. The
following will be displayed:
Highest (Lowest) Tap
16 C
6.
Utilizing the Up/Down arrow pushbuttons, enter the desired Highest (Lowest) Tap
value, then press the ENT pushbutton.
6.4.1.14
Setting Highest and Lowest Tap from TCC600
To set the Highest Tap and Lowest Tap setting from TCC600®, perform the following:
This setting is applicable to Reg External #1 and #2, and XFMR External
#1, #2 and #3, modes of Tap Information.
1.
Select
Setup/Tap Settings
from the TCC600 toolbar. TCC600 will display the Tap
Settings dialog screen.
1VAC388793-MB A
Section 6
Configuration
TCC300
469
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......