X.XXX LEAD/LAG
Displays the real-time calculated value of power factor.
Frequency
XX.X Hz
Displays the line frequency.
10.2.1.2
Present Demand
Demand Interval
XX Min
Toggles between 5, 10, 15, 30 and 60 minute interval with a factory setting of 15 minutes.
The time interval is the amount of time it takes for a thermal meter to indicate 90% of a
change of load.
Demand Load Voltage
XXX.X Volts
Displays the real-time measured value of voltage at the regulator or transformer. This
value continuously averaged over consecutive 32-second intervals.
Demand Pri. Current
XXX.X Amps
Displays the calculated primary demand current based on the user-selected current
multiplier and measured secondary current.
Demand Pri. Watts
X.XX MW
Displays the demand value based on the user
‑
selected voltage and current multipliers or
secondary voltage and current.
Demand Pri. VArs
X.XX MVArs
Displays the demand value based on the user
‑
selected voltage and current multipliers and
measured secondary voltage and current.
Demand Pri. VA
1VAC388793-MB A
Section 10
Appendix A HMI
TCC300
605
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......