4.
Press the Down arrow pushbutton, as necessary, until the "VAr Bias Method" screen
is displayed.
5.
Press the ENT pushbutton. If prompted, enter a valid Level Access Code. The
following will be displayed:
Set VAr Bias Method
disable C
6.
Utilizing the Up/Down arrow pushbuttons, select "STEP", then press the ENT
pushbutton. The following will be displayed.
Set VAr Bias Method
STEP
7.
Press the Up/Down arrow pushbuttons, as necessary, to navigate to the "Disable on
Rev Pwr" menu item.
8.
Press the ENT pushbutton. If prompted, enter a valid Level Access Code. The
following will be displayed:
Disable on Rev Pwr
disable C
9.
Utilizing the Up/Down arrow pushbuttons, select either "Enable or disable", then
press the ENT pushbutton.
10. Follow the procedure above to enter the desired:
•
Forward Max Cap Bank Size
•
Reverse Max Cap Bank Size
•
Lead % Pickup
•
Lag % Pickup
•
VAr Bias Voltage Step
•
Max VAr Bias Time
7.8.1.2
Enabling Step VAr Bias Method from TCC600
1.
Select
Setup/Setpoints
from the TCC600® toolbar. TCC600 will display the
Setpoints dialog screen.
Section 7
1VAC388793-MB A
Setpoints
542
TCC300
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......