for the control to operate. All automatic Raise/Lower tap operations are blocked, when
input voltage is less than 85.0 Vdc.
Runup Deadband
X.X Volts
Runup Deadband is adjustable from 1.0 V to 4.0 V in 0.1 V increments with a factory
setting of 2.0 V.
Runup Enable/Disable
disable
Enables or disabled the Voltage Runup feature.
Current Block Limit
XXX mA
Current Block Limit is adjustable from 50 mA to 640 mA in 1 mA increments with a
factory setting of 640 mA with hysteresis of 5 mA. If the value of the current exceeds the
Current Block Limit setpoint, the unit will not permit automatic control.
10.2.2.7
VAr Bias
Set VAr Bias Method
disable
Enables either "Step" or "Linear" VAr Bias method or disables the VAr Bias feature.
10.2.3
VAr Bias
10.2.3.1
VAr Bias (Step)
Disable on Rev Pwr
disable
Allows Step VAr Bias to be disabled in the reverse power mode.
Fwd Max Cap Bank Size
12000 KVAr
Sets the largest capacitor bank size in the forward mode from 4 to 12,000 KVAr.
1VAC388793-MB A
Section 10
Appendix A HMI
TCC300
619
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......