
GUID-F30E8D82-95A5-4460-AAEE-BBCD9FAD3FEB V1 EN
Figure 319:
Setpoints Successfully Written To The Control Dialog Screen
6.2.16
Remote voltage bias
The Remote Voltage Bias (RVB) feature is similar to Load Drop Compensation (LDC)
that biases the Bandcenter of the control using the difference between a remotely
monitored voltage and the control's Load voltage. This method allows the control to
operate using the existing timing as well as allow it to respond to the blocking limits and
runback functions.
The TCC300 will regulate the measured voltage according to a calculated Effective
Bandcenter. The Effective Bandcenter will ONLY be calculated when a Remote
measurement is supplied to the control. The Effective Bandcenter calculation is based on
the following equations:
BC
= V
BC
bias
remote
−
GUID-1CFA423F-068F-4A7D-A740-796321CC76DB V1 EN
(Equation 5)
BC
bias
Bandcenter bias
V
remote
Remote voltage
BC
Bandcenter setting
EffBC = (V
BC
)
i
measured
bias
−
GUID-B8A247C8-6628-4457-9BBE-E90064B03F06 V1 EN
(Equation 6)
EffBC
i
Effective Bandcenter
V
measured
Measured secondary voltage
BC
bias
Bandcenter bias
1VAC388793-MB A
Section 6
Configuration
TCC300
389
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......