GUID-F30E8D82-95A5-4460-AAEE-BBCD9FAD3FEB V1 EN
Figure 363:
Setpoints Successfully Written To The Control Dialog Screen
5.
If "INTERNAL KEEPTRACK" was selected, then proceed to "Initializing Tap
Position When Motor Direct Drive KeepTrack™ is Active" in this section.
6.
If an External Tap Position or Contact KeepTrack™ 1R1L/1N method was selected
in Step 7, then proceed to "Initializing Tap Position when Regulate (Reg or XFMR)
External or Contact KeepTrack is Active" in this section.
6.4.1.8
Contact KeepTrack
™
1N – Additional TCC600 settings screen
When Contact KeepTrack 1N is selected as the Tap Information method, an additional
Contact KeepTrack 1N Tap Configuration window becomes available. The Contact
KeepTrack 1N method of Tap Position knowledge can function with any combination of
taps and multiple neutrals, or with the neutral assigned to a non-zero tap.
1VAC388793-MB A
Section 6
Configuration
TCC300
461
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......