GUID-2EDBFD25-222B-4846-9AA2-CDFA5AE21B47 V1 EN
Figure 386:
Tap Settings Dialog Screen
2.
Enter the desired "Normal Voltage" (100.0 to 130.0 Volts) value.
3.
From the "CBEMA Event 1" section of the dialog screen select ENABLE, then enter
the following settings:
•
Event 1 Sag Pickup
•
Event 1 Sag Dropout
•
Event 1 Sag Minimum Duration
4.
Repeat Step 3 to setup Events 2, 3, 4.
5.
Select
Save
. TCC600 will display a "Do you want to enable CBEMA Sequence of
events?" confirmation screen.
GUID-07992690-3288-489C-89D1-3A411C72C417 V1 EN
Figure 387:
CBEMA Sequence of Event Enable Confirmation Screen
6.
If CBEMA Events are to be used to trigger the Sequence of Events recorder, then
select "Yes". TCC600 will display the Sequence of Events Setup dialog screen.
CBEMA Event and counter status can be observed on the Metering
and Status screen
Section 6
1VAC388793-MB A
Configuration
486
TCC300
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......