Tapchanger Type
3.
Press the Right or Left arrow pushbutton, as necessary, to navigate to the "Mtr
Current Profile" menu.
4.
Press the Down arrow pushbutton, as necessary, to navigate to the "Peak RMS %
Change" (Average RMS Current % Change or Average Duration % Change)
settings dialog screen.
5.
Press the ENT pushbutton. If prompted, enter a valid Level 2 Access Code. The
following will be displayed:
Peak RMS % Change
110 C
6.
Utilizing the arrow pushbuttons enter the desired Peak RMS Current % Change
value (110% to 200%), then press the ENT pushbutton.
6.2.14.2
Setting the Motor Current Detection Settings from TCC600
1.
Select
Setup/Configuration
from the TCC600 toolbar. TCC600 will display the
Configuration dialog screen.
GUID-6C74AD06-67C3-433B-B783-6A218088FA6D V1 EN
Figure 313:
Configuration Dialog Screen
2.
From the "Motor Current Settings" section of the dialog screen enter the desired
Peak RMS Current, Average RMS Current and Average Duration settings (110% to
200%).
3.
Select
Save
. TCC600 will display a "Confirm Writing to Device" confirmation
screen.
Section 6
1VAC388793-MB A
Configuration
384
TCC300
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......