Verify that a "Regulate (Reg or XFMR) External" mode is selected in the "General"
section of the dialog screen.
In order to verify Neutral Tap Position, when the tap position is "0",
but no neutral input is detected, the Tap Position screen of the
TCC300 will display "- - -" instead of "0". When reading the tap
position via comms (Modbus and DNP) a value of 32767 will be
returned when the tap position is "0", but no neutral input is detected,
otherwise a "0" will be returned.
3.
Determine and note the actual tap position from the external tap position indicator on
the regulator or transformer.
4.
Enter the tap position noted in Step 3, then select "Yes" for Tap Calibrate.
5.
Select
Save
. TCC600 will display a "Confirm Writing to Device" confirmation
screen.
1VAC388793-MB A
Section 6
Configuration
TCC300
467
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......