1000
The time period allocated to read all the paralleled units' relevant data, make the necessary
calculations and disseminate paralleling driven updates to the system (Range 1000 to
10000).
Load Side Brk Config
Not Used
Can be set to Not Used, 52a (positive polarity), or 52b (negative polarity).
Right Tie Brk Config
Not Used
Can be set to Not Used, 52a (positive polarity), or 52b (negative polarity).
Left Tie Brk Config
Not Used
Can be set to Not Used, 52a (positive polarity), or 52b (negative polarity).
MVA Rating
1.0
The MVA rating of the transformer (Range 1.0 to 1000.0).
I Multi Correction
xxx %
A scaling factor to compensate Delta Vars Calculation, if the CT value is not in the ratio
to the MVA rating (Range 20 to 500 %).
Clear Lockout Alarm
Ready Press ENTER
Allows reset of lockout alarm at control front panel.
10.2.4.4
Programmable Alarm
Prog Alarm Function
–<0000000000000000
1VAC388793-MB A
Section 10
Appendix A HMI
TCC300
629
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......