Master Reset
10.2.1.5
Status
Press ENT to view
Tapchanger Status
TAP BDS PWR BLK VRD
1 OK fwd --- Off
•
TAP Tap Position
[1]
•
BDS Band Status (Lo, Hi, OK)
•
PWR Power Direction (Fwd, Rev)
•
BLK Blocks in Effect
•
VRD Voltage Reduction (Off, 1, 2, 3)
Press ENT to view
Alarm Status
A B C D E F G H I J K L M N O P Q R S T
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
•
A = Block Raise Tap
•
B = Block Lower Tap
•
C = Block Raise Voltage
•
D = Block Lower Voltage
•
E = Voltage Reduction
•
F = Power Direction
•
G = Current Limit
•
H = Comm Block
•
I = LDC/LDZ
•
J = Abnormal Tap
•
K = VAr Bias Lag
•
L = VAr Bias Lead
•
M = Backup Fail (If purchased)
•
N (M
[2]
) = DVar2 Over Curr (If purchased)
•
O (N
[5]
/M
[3]
) = Seal-in Failure
•
P (O
[5]
/N
[3]
) = Low Current Blk
[1] In order to verify Neutral Tap Position, when the tap position is "0", but no neutral input is detected, the Tap Position screen will display "- - -"
instead of "0".
[2] These parameters will decrement by 1 letter if Backup Power (M) is not purchased.
[3] These parameters will decrement by 2 letters if Backup Power (M) and DVAr2 (N) are not purchased.
Section 10
1VAC388793-MB A
Appendix A HMI
608
TCC300
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......