Press ENT to begin
Resets the Run Through Neutral Success Counter.
Max Allowed Taps
x
The Maximum Allowed Taps Setting (3 to 7) determines the maximum number of taps
that can be taken to swipe the reversing switch.
Taps Between Runs
xxxxx
This setting (10 to 10000) establishes the number of taps that must be taken before the Run
Through Neutral Feature is activated.
Max Load Current
xx mA
Establishes the Maximum Measured Load current value (1 to 200 mA) that Load Current
must be less than to allow the Run Through Neutral feature to activate.
Max RTN Standby Ops
xxxxx
The Maximum RTN Standby Operations setting (1 to 10000) is the number of Tap
Operations that when exceeded initiates the "RTN Fail to Operate" alarm.
10.2.4.13
Remote Voltage Bias
Enable/Disable
disable
Enables and Disables the Remote Voltage Bias Feature.
RVB HB Timer
xxx
The Remote Voltage Bias Heartbeat Timer setting (2 to 120 sec) is the period that upon
receiving the remote voltage value the voltage bias is applied to the Bandcenter. If no
remote voltage value is received and the timer times out the control will revert to existing
settings.
Section 10
1VAC388793-MB A
Appendix A HMI
640
TCC300
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......