Item
Description
Indicates when the VAr Bias effect (Lead or Lag) has
exceeded the time limit imposed by the Max VAr Bias
Duration Setting.
There are two types of lockout conditions, Master
lockout and Follower lockout. Any lockout of the
paralleling mode will set the Master/Follower
Lockout Alarm. When a lockout condition exists, the
control issuing the lockout will stop any further
GOOSE publishing and will stop load voltage
regulation. Also, the alarm can be configured as a
DNP event, or as a report in case of IEC 61850. The
lockout state will be displayed on the control front
panel display and in the Master/Follower
Configuration Tool.
Master/Follower Alarm
messages can be observed for
the connected control from the
TCC600® Monitor/Master/
Follower Alarm messages menu
item.
Table continues on next page
Section 4
1VAC388793-MB A
TCC600
158
TCC300
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......