GUID-C05B6A4F-FD6A-492E-8F52-FDC5D31F6722 V1 EN
Figure 131:
Data Log Download Dialog Screen
Clear
This submenu item when selected, clears the data logging information stored in the
control.
4.10.5.9
Harmonics Setup
The Harmonics Setup dialog screen provides the user with the ability to select Voltage and
Current Harmonics for monitoring relative to a Voltage and Current threshold setting.
Whenever any selected Voltage or Current Harmonic exceeds their respective threshold
if selected in Sequence of Events setup will initiate Sequence of Events recording. The
threshold level is set as a percentage of the fundamental.